Is it possible for connecting a non-incendive Ex nA digital indicator to an intrinsically safe Ex i sensor in hazardous areas? Frequently, signals from pressure sensors that not have a built-in digital indicator for the measured value are connected to external digital indicators. These digital indicators enable an on-site display of the measured value and, thus, a convenient and immediate reading of, for instance, the level in storage vessels.
Pressure sensors for hazardous areas are generally designed with the ignition protection type ?intrinsically safe?, since this enables interventions within an active electrical circuit and less energy is necessary. However, this also implies that there’s insufficient energy designed for a robust measured value display. Due to this fact, digital indicators tend to be made with ignition protection types that enable more current and voltage to be allowed. Frequently, digital indicators are designed as ?non-incendive? (Ex nA). This ignition protection type enables power-hungry instruments to be operated in Ex areas too. However, Ex nA is limited for used in zone 2 ? so in areas in which an explosive atmosphere only rarely occurs.
The right connection of digital indicator and barrier
Non-permissible connection of an Ex i pressure sensor with isolated barrier and Ex nA digital indicator.
Every Ex i sensor requires an intrinsically safe barrier for its voltage supply, in order that the interconnection is considered as intrinsically safe and the huge benefits, such as maintenance work without the need for a fire certificate, can be used. Digital indicators are frequently integrated as passive element, with or lacking any external power supply, directly in the 4 ? 20 mA current signal of a sensor. Since an Ex nA digital indicator does not have any Ex i performance data in its approval, it cannot therefore be utilized in a ?Proof intrinsic safety?. Therefore, an Ex nA indicator can’t be connected within an Ex i circuit.
Correct connection of an Ex i pressure sensor with isolated barrier and Ex nA digital indicator.
There is, however, the chance to connect a digital indicator having an Ex i pressure sensor in zone 2. The prerequisite is that the intrinsically safe isolated barrier also possesses an Ex nA approval and should be installed in zone 2.
Read also pressure gauge weksler ราคา and intrinsically safe pressure sensors ? an inseparable pair
Proof intrinsic safety for an ATEX-approved pressure sensor
Note
In the event you need any help with choosing a suitable solution for your pressure measurement requirement, your contact person will gladly be of assistance.