FIRE SUPPRESSION

Petroleum Storage Tank Facilities – Part 3

by Brenna ShumbamhiniJune 9, 2022

Share

In earlier installments of this sequence we talked in regards to the types of petroleum storage tanks, their areas, common hearth hazards, described the kinds of fires, and fireplace suppression systems that storage tanks might have.
In this third and last article we are going to focus on firefighting strategies and tactics in addition to pre-incident response planning basics.
Firefighting Strategies and Tactics

Firefighting methods and techniques begins with a properly deliberate and tested pre-incident response plan. This will be mentioned later in the article. Storage tank fires are advanced events. These fires will require the implementation of plans, preparation, proper utilization of assets, and an in depth logistics part to ensure the sources can be found and arrive on scene in a coordinated and timely fashion. The following methods and ways for firefighting presume that the planning and preparation stages have been carried out by plant and hearth division personnel. Experience tells us that profitable and protected extinguishment of tank fires can only be achieved when based mostly on planning and preparation, with all related participating in all aspects of the process in addition to the exercising of the plan. Exercising the plan can be carried out with desk high situations as nicely as periodic full scale exercises.
As quickly as a hearth department receives notification of an incident, size up and intelligence gathering should be started. Information must be gathered quickly to start the development of firefighting methods. The following ought to be considered:
Rescue of personnel in the immediate space

Life security hazards to web site personnel

Extension

Confinement

Extinguishment

Environmental influence

Community influence

After the quick issues are addressed, we need to establish the sort of fire present:
Vent hearth

Seal fire

Piping-connection fireplace

Full floor involvement fireplace

Once we have examined the above information we can then begin to develop our resource record and incident action plan (IAP). Remember that the sort of product concerned will also impression our resource needs and techniques. The following are numerous types of fires and firefighting tactics:
Ground Spill or Dike Fires

These fires could be viewed as simple pool or spill fires. Calculate the realm (length x width) and use the proper application price based on NFPA eleven, Standard for Low-, Medium-, and High-Expansion Foam. Knowing the product will also give you the appropriate kind of foam focus and application method. Alcohol merchandise would require a gentle utility method. Firefighters mustn’t enter the dike space unless safe to take action and accredited by the Incident Commander in consultation with the incident’s Safety Officer. Atmospheric testing must be performed previous to and through entry. Exposures corresponding to tanks, related piping, and pumps must be protected with water by way of ground or fixed screens. Ground fires must be extinguished first, then utilizing dry-chemical tools, valves and flanges extinguished. The handiest tools for these mixed fires could be hydro-chem™ know-how whereby foam/water resolution as well as dry-chemical could be delivered concurrently by way of the same nozzle.
Specialized moveable monitor positioned on lip of storage tank.
Rim Seal Fires

Rim seal fires can usually be extinguished using the mounted or semi-fixed foam methods if put in and correctly maintained. On external floating roof tanks, if the fastened or semi-fixed fire safety methods are not present, handbook firefighting will need to be carried out. Under the protection of a water spray, a firefighting crew will ascend to the gauging platform with hand-held foam tools. The main technique must be using foam wands to seize the hearth (Photo 1- Foam Wand) which permits the placement of specialised displays to be placed on the lip of the tank. (Photo 2- Specialized transportable monitor) The displays can then be used to extinguish the rim seal fire using the attain of the monitor in order that hoselines and personnel are not working from the wind girder away from the ladder. If this gear is not obtainable, then foam hoselines might be used from the wind girder. This is a hazardous operation, and only undertaken if there’s a structurally secure wind girder with handrails. (Photo 3- Foam chamber and Wind Girder) Personnel ought to be secured to forestall falling.
In some instances, elevated streams from hearth vehicles have been used. This isn’t a major method of extinguishment. It has been noted that there is at all times a chance of sinking or tilting the roof under the excess water/foam solution, thus creating a bigger problem, which may include an obstructed /unobstructed full surface hearth.
On tanks fitted with inner floating roofs, these fires could additionally be thought of uncommon, but they do happen. They might be extraordinarily difficult to extinguish except fastened or semi-fixed hearth safety systems are put in. Foam chambers and foam dams are the simplest, and the design of the system should be calculated on a full floor fireplace, particularly if the pan below is aluminum.
The most troublesome methodology of extinguishment in a covered floating roof tank shall be to shoot foam water resolution via the eyebrow vents. Using hydro-chem™ into these vents has confirmed effective prior to now.
Full Surface Fires

Staffing necessities for a major tank hearth will vary depending on the kind of tank, location, water supplies, nature of the incident and the provision of trained personnel. Attacks on these fires will predominantly use the Type III “Over the Top” technique of extinguishing agent delivery. The product concerned will decide the required foam software price and proportion of focus to water flowed. The size of the tank may even determine the application fee. For larger tank diameters a bigger application price is required. The chart under is accepted by industry consultants to be the minimum utility charges based mostly on the tank diameter:
Table 1– Application rates

Foam resolution (foam concentrate + water) flow charges to be established are based on the next formulation:
Foam answer circulate fee = Tank surface area x software fee (as famous in desk 1)

Tank surface area = three.14 x radius2

Application fee = as per table below

Foam Concentration Flow Rate (lpm [gpm] of froth concentrate)

Foam concentrate circulate fee = Foam answer flow price x foam percent

Foam percent = 1%, 3%, 6% depending on type of foam, product on fireplace and manufacturer’s recommendations

Foam Concentrate Quantities

Foam focus flow price (lpm or gpm) x period

Duration = sixty five minutes for Type III (over the top) purposes

Please note that these portions are for extinguishment functions. For vapor suppression after extinguishment it’s an accepted follow to double our extinguishment supplies to maintain up the suppression of vapors and stop the potential reignition of the product.
Some of the above flows may be nicely in extra of 37,854 lpm (10,000 gpm) and would require giant capacity delivery units such as massive trailer mounted monitors and large portable pumps.
Now that we all know our circulate charges and foam concentrates required we have to additionally look at other components similar to:
Position and situation of roof drains

Volume of the product

Status of tanks and valves

Depth of water bottoms

Structural situation of tank

Product in tank and its bodily properties

Is there room within the tank to merely accept the whole foam resolution without causing an overfill

What other tanks, piping, or structures could also be exposed

Wind direction

Weather circumstances (present and expected)

Foam chamber on tank. Note the wind girder with appropriate handrail. If the froth chamber was not current or did not perform correctly, the wind girder could be used to advance foam hoselines for seal fireplace extinguishment.
In any fire scenario we wish to contain the native facility personnel in our planning part as technical specialists. They may also be on the command post advising the Incident Commander instantly. These fires usually are not our ordinary ‘bread and butter’ operations and ought to be handled as an incident that can change rapidly and unexpectedly, often with severe penalties. Do not try and extinguish a full floor fire without all essential resources on the scene. Cooling of adjacent tanks would be a tactic to be used previous to all foam delivery and personnel assets are on the scene. The cooling of the tank that’s on fireplace just isn’t recommended except full 360 diploma cooling can be accomplished, which is rare. Also, when cooling a tank, use only the quantity of water necessary. When the cooling water stops turning to steam, you might shut down the streams and start them up again when necessary. This will preserve water supplies for extinguishment and cut back the water flowing into the dike areas. Generally between 1,893 lpm (500 gpm) and 3,785 lpm (1,000 gpm) shall be required for each tank cooled. In addition to the correct supply units and foam supplies, we need to ensure that our foam resolution delivery zone on the floor will be succesful of unfold out once it hits the floor and canopy the complete floor area. According to the National Fire Protection Association (NFPA) foam can journey successfully across at least 30m (100 ft) of burning liquid. We consider that for calculating foam runs, this quantity ought to be decreased to 24m (80 ft), guaranteeing that our landing zones journey and overlap each other. Firefighters ought to be aware of the gap a master stream can attain in addition to the landing zone length and width. These may be obtained from the manufacturer of the screens and nozzles and verified within the subject throughout drills and exercises. By understanding this information we will pre-plan the positioning of our grasp streams. Range finders can be used throughout operations to gauge distances to the tank to help with monitor positioning. There are a couple of occurrences that may occur at a storage tank fireplace that the fire service ought to concentrate on. These are:
Slopover

This event can occur when a water stream is applied to the new surface of burning oil, offered that the oil is viscous and the temperature exceeds the boiling point of water. It causes a brief period of slopping of froth over the rim of the tank with a minimal of depth.
Frothover

Frothover is a gradual, slow transferring froth over the rim of a tank and not utilizing a sudden and violent reaction. Frothover might happen when the tank just isn’t on fireplace and water already contained in the tank is out there in contact with hot viscous oil which is being loaded. An example is when scorching asphalt is loaded right into a tank automotive and comes into contact with water within the tank, causing the product to froth over the top. During a fire with crude oil it might also happen when the warmth wave created by the burning crude oil reaches the water layers (stratums) within the crude oil. This heat wave will convert the water to steam, inflicting a frothover.
Boilover

This occasion is a sudden and violent ejection of crude oil from the tank as a end result of reaction of the hot-layer and the buildup of water at the backside of the tank. The mild fractions of crude oil burn off, producing a heat wave within the residue. The residues with their associated heat wave sink in path of the underside of the tank. This warmth wave will finally reach the water that normally accumulates at the backside of the tank, and when the 2 meet the water is superheated and subsequently boils, expanding explosively inflicting a violent ejection of the tank contents and fire. The expanding contents being expelled can journey the gap equivalent of ten tank diameters. Careful consideration must be given during pre-incident response planning of the placement of the command submit, staging areas, rehab, gear placement, etc.
Pre-Incident Response Planning

When planning for a response to a petroleum storage tank facility it is best that the knowledge gathered is completed on-site and with the assist of facility personnel. While on web site, entry roads that you would be use to access the realm and position fireplace equipment (appliances) should be pushed by the autos that might be used throughout an incident. Many times the turning radius of apparatus is too nice to make the turns needed within the facility. Swales or culverts may impede equipment. If the equipment chassis is simply too lengthy and or low, it may hang up or floor whereas traversing a swale or culvert. Bridges on web site may not allow the load restrict of recent apparatus, stopping its use at an incident.
During pre-incident response planning data that ought to be gathered includes the next:
Tank varieties, dimensions, contents and capacities

Pipe isolation valves, locations, and operating mechanism

Fixed fireplace safety techniques out there

Access factors to facility and tank

Contact cellphone numbers

Locations and operation of emergency shutdown gadgets (ESD’s)

Availability of firefighting resources

Water provides

Pumping necessities

Foam focus necessities

Mutual/automatic assist out there

Other information may be obtained based mostly on the wants and necessities of your department. While these articles are not totally inclusive of all info that a hearth division needs to know, it’s a good begin. Other resources are listed at the finish of this text. It is essential that firefighters attend classes on this specialized firefighting, pre-plan these facilities, and train the pre-plans. Don’t allow these facilities to turn out to be part of the panorama. Visit pressure gauge 0 10 bar ราคา and ask questions!

For more data, go to www.worldsafeinternational.com

[su_note]Resources

American Petroleum Institute [API]. API Recommended Practice 2021: Management of Atmospheric Storage Tank Fires. Washington, DC: API, 2001, Reaffirmed 2006 Hildebrand, M. S. & Noll, G. G. Storage Tank Emergencies: Guidelines and Procedures. Annapolis, MD: Red Hat Publishing, 1997 Institution of Chemical Engineers [IChemE]. BP Process Safety Series: Liquid Hydrocarbon Tank Fires: Prevention and Response. Rugby, UK: IChemE, 2005 Shelley, C. H., Cole, A. R. and Markley, T. E. Industrial Firefighting for Municipal Firefighters. Tulsa, OK: PennWell, 2007References 1.
Shelley, C. H., Cole, A. R. and Markley, T. E. Industrial Firefighting for Municipal Firefighters. Tulsa, OK: PennWell, 2007.[/su_note]

Top Image:- Foam wand being placed during coaching. Note the protecting hose stream in place.